Skip to main content

KAL710

Kilsen Addressable Zone Monitoring Units - 1 Zone
  • EN54:18 and CPD certified
  • Surface mount with high IP rating for increased protection
  • Easy addressing
  • Externally powered for reduced loop current
  • Local alarm and communications indication
View all

At a glance

General

The KAL700 series modules include a complete range of interfaces developed for I/O control on addressable fire systems running Kilsen protocol, housed in easy to install, IP55 housings. These modules allow the fire system to perform additional building management functions during fire situations. 125 I/O addresses are available on every fire panel loop in addition to 125 fire detector addresses.

KAL700 Conventional Zone Monitors

The KAL710 allows for the connection of one, the KAL714C up to four, conventional fire detector zones to the addressable fire system loop. Up to 20 conventional detectors or up to 32 conventional manual call points may be connected to every zone. These units allow differentiation of call point alarms from detector alarms for mixed zone applications.

The KAL710 and KAL714C provide power to the fire detector zone(s) from an external 24 VDC source, and digitally communicate the status of every zone to the fire panel. A LED on every module indicates the alarm and communication status of the module locally.

Installation

The KAL700 Series is designed for surface mount installation. Addressing on the modules is done via easy to use DIP switches.

Applications

The KAL710/KAL714C zone monitoring units are normally used in situations where an area to be covered does not require any sub-divisions or does not require a particular fire point recognition.

They may also be used for retrofit installations where a conventional system is replaced by an addressable system during a phased upgrade i.e. where not all conventional detectors are replaced immediately by addressable devices. Existing
conventional devices may in these cases still be used with the new Kilsen addressable system.

The KAL710/KAL714C is designed to be used with Kilsen conventional detectors, but may also be used as an interface to connect with other compatible, industry standard, conventional detectors.

Details

  • EN54:18 and CPD certified
  • Surface mount with high IP rating for increased protection
  • Easy addressing
  • Externally powered for reduced loop current
  • Local alarm and communications indication
  • Full supervision of one conventional fire zone
  • Part of a family of I/O modules consisting of: -Conventional zone monitors -Digital input modules -Loop Isolators -Manual call points -Relay and supervised output units -Fire door controllers

Technical specifications

General
Status indication
LED
Compatibility
Kilsen KL7A systems
Electrical
Power supply type
24 VDC
Operating voltage
22 to 38 VDC
Current consumption
90 µA @ 24 V from the loop (Quiescent)
105 µA @ 35 V from the loop (Quiescent)
< 3 mA from the loop (Alarm)
200 µA external (Quiescent)
< 85 mA external (Alarm)
Input
Input quantity
1
Input type and rating
Supervised conventional zone
Termination resistor
4.7 kΩ
Physical
Physical dimensions
182 x 142 x 77 mm
Net weight
370 g
Colour
Grey
Mounting type
Surface mount
Cable entries
10
Environmental
Vandal proof
No
Operating temperature
-10 to +50°C
Storage temperature
-10 to +70°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP55
Regulatory
Compliancy
CE
REACH
RoHS 2
WEEE
Certification
CPR
Standards
EN54-18

Compatible products

Category Reference Description
Interface unit KAL714C Kilsen Addressable Zone Monitoring Units - 4 Zones
Interface unit KAL730 Kilsen Addressable Relay Output Module - 1 Output
Interface unit KAL734C Kilsen Addressable Relay Output Module - 4 Outputs
Interface unit KAL740 Kilsen Addressable Supervised Relay Output Module - 1 Output
Interface unit KAL760 Kilsen Addressable Input Module - 1 Input
Interface unit KAL775 Loop Isolation Module