Skip to main content

NC-PF4-SC

Conventional Fire Panel with Scandinavian Key - 4 Zone
  • Modern, elegant design with basic and intuitive user interface with icons.
  • Easy removable parts for quick and clean installation
  • Default regional setup modes
  • Normal, head-out & intrinsically safe zone support
  • Supervised alarm notification & fire protection outputs
View all

At a glance

Overview

The New Conventional fire control panels offer state of the art architecture in configurations that deliver an uncomplicated solution for small to mid-sized conventional applications. With their clean and attractive contemporary design, they fits with any decor. The basic and intuitive user interface with icons make easy their application everywhere without an additional language kit required.

With support for multiple lines of conventional detectors and accessories, these quick-to-configure systems offer versatility that benefits building owners and installation/maintenance companies alike.

The Panel

The NC-PF4-SC is a conventional fire alarm control panel with Scandinavian key support. It is supplied with 4 zones that support up to 32 devices per zone, as well as up to 4 supervised relay outputs dedicated to sounder control and fire routing. In addition 2 conventional relay outputs dedicated to common fire and fault conditions, as well as two user configurable inputs for monitoring and control are available.

Options

The panels support 2 types of auxiliary relay boards, one with 4 standard relays, and one with 4 supervised relays. With these boards the panel outputs may be expanded with up to 8 additional outputs.

Approvals & Compliance

The product line carries the following accreditations:

• EN54:2, EN54:4 and CE approved
• CPD certified
• NEN2535, NBNS21-100 and BS5839-1 compliant

• WEEE compliant
• RoHS compliant

Type class conditions: 3K5 of IEC 60721-3-3

Details

  • Modern, elegant design with basic and intuitive user interface with icons.
  • Easy removable parts for quick and clean installation
  • Default regional setup modes
  • Normal, head-out & intrinsically safe zone support
  • Supervised alarm notification & fire protection outputs
  • EN54 compliant potential free fire & fault relays
  • Class change, day/night, remote reset, extended fire routing delay & fire routing inhibit delay facilities
  • Auxiliary 24VDC supply output with reset support
  • Default support for special functions such as: - EN54 compliant user access levels - mixed zones - full front panel diagnostics - one-man walk test - CleanMe™
  • Auxiliary standard & supervised relay output boards
  • Networkable up to 64 zones
  • No language kit inserts required

Technical specifications

General
Maximum system capacity (device count)
up to 1280
Network size (nodes)
up to 16
Electrical
Power supply type
VAC
Power consumption
2 A @ 24 VDC
Operating voltage
110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
Cable type: 3 x 1.5 mm² (live, neutral, earth)
Current consumption
2 A @ 110/240 VAC
140 mA (alarm, no devices) (panel supply)
60 mA (quiescent, no devices) (panel supply)
Loop
Maximum loop capacity
4
Zone
Maximum zone capacity
up to 4
Operating voltage
22 VDC (18 to 24 VDC)
Quantity of devices per zone
32 max.
Rating
65 mA (max. Load)
Cable rating
40 ohm (max. cable resistance), 500 nF (max. cable capacitance)
Input
Input quantity
2
Input type and rating
100 ohm (max. Cable resistance)
Output
Supervisory voltage
-15 to +28 VDC
Auxilliary power
24 VDC (21 to 28 VDC)
Supervised Outputs 4
Load (max.) 250 mA
Non Supervised Outputs 2
Load 2 A @ 30 VDC
Standby battery
Capacity
2 x 12 V, 7.2 Ah (SLA)
Physical
Form factor
Small
Physical dimensions
320 x 435 x 134 mm (W x H x D)
Net weight
2.8 kg (without battery)
Shipping weight
4.5 kg
Colour
Grey (RAL 7035)
Mounting type
Surface mount
Cable entries
Ø 20 mm - 14 / 2 / 12 (top / bottom / rear)
Environmental
Operating temperature
-5 to +50°C
Storage temperature
-20 to +70°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP30
Regulatory
Compliancy
CPD
RoHS
WEEE
Certification
EN54-2
EN54-4
Auxilliary Supply Output
Load (max.) 250 mA @ 25°C / 195 mA @ 40°C