KFP-AF1
KILSEN Addressable Fire Panel - 1 Loop
- 1 loop with up to 512 zones
- Up to 40 LED Zone indicators for Fire and Fault with ample text space
- Auto configuration and default regional setup modes
- Ethernet port with TCP/IP for remote maintenance and programming
- EN54 compliant graphical LCD with icons and up to 256 zones
Alternative products
At a glance
Overview
The KFP-A Series life safety control systems are bringing the speed and functionality of high-end intelligent processing to small to mid-sized addressable applications. They feature an attractive contemporary design that fits with any decor. Special plastics allows for painting in any color and the easy to remove electronics will support in this matter. The gently curved door with the intuitive dark inset user interface and EN54 compliant graphical LCD offers a distinctive flair. The main controls are clearly, but discreetly highlighted with the focus on the central located Jog Dial.
With the addressable detection and a full line of easily configured option cards and modules, USB and Ethernet® connectivity, these quick-to-configure systems offer versatility that benefits building owners and life safety system installers alike.
With the addressable detection and a full line of easily configured option cards and modules, USB and Ethernet® connectivity, these quick-to-configure systems offer versatility that benefits building owners and life safety system installers alike.
The Panel
The fire panels supplied in local language, with user interface, with 1 loop that supports up to 250 devices in 512 zones, have standard 2 supervised sounder/fire-routing outputs, which can be used as freely programmable outputs as well. In addition 2 conventional relay outputs and 2 supervised outputs, working in pair and dedicated to common fire and fault conditions, as well as 2 user configurable inputs for monitoring and control are available.
Options
The panels supports one network board to create a maximum of 32 nodes / 32 loops network of fire panels, fire panel repeaters (including conventional fire panels and fire panel repeaters up to a maximum of 64 conventional zones). Last but not least, in case seperate zone indications are required, a 20 or 40 zone fire/fault LED indicator board can be mounted in the panel or repeater with ample space for text.
Approvals & Compliance
• CE / CPD / EN54-2 / EN54-4
• NEN2535 / NBNS21-100 compliant
• BS5839-1 compliant
• VdS and LPCB certified
• WEEE / RoHS compliant
• NEN2535 / NBNS21-100 compliant
• BS5839-1 compliant
• VdS and LPCB certified
• WEEE / RoHS compliant
Details
- 1 loop with up to 512 zones
- Up to 40 LED Zone indicators for Fire and Fault with ample text space
- Auto configuration and default regional setup modes
- Ethernet port with TCP/IP for remote maintenance and programming
- EN54 compliant graphical LCD with icons and up to 256 zones
- Jog Dail with 4 soft buttons for simple and intuitive user control
- Aesthetic pleasing design with special paintable synthetic door
- Easy removable door and chassis for quick and clean installation
- All pluggable connectors
- 3 USB ports with memory stick support
- 3 RS232 ports
- Auxiliary 24VDC supply output with reset support
- 3 operator level menu structure
- History log memory for 9999 events
- Up to 72 hours standby time and 30 minutes alarm
- Compatible with the KL700A series detectors with replaceable optical chamber and loop powered sounders and base sounders
Technical specifications
| General | ||
|---|---|---|
| Maximum system capacity (device count) |
up to 16000
|
|
| Network size (nodes) |
up to 64
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
VAC
|
|
| Operating voltage |
110/230 VAC (+10%/-15%), 50 / 60 Hz (±5%)
Cable type: 3 x 1.5 mm² (live, neutral, earth)
|
|
| Current consumption |
Nom. 0.6 / 1.3 A, Max. 1.5 / 3.15 A
2 / 4 A (Fuse rating)
|
|
| Loop | ||
|---|---|---|
| Maximum loop capacity |
1
|
|
| Cable rating |
56 ohm, 1 µF, max. 4 km, Cable type: Recommended 2 core 1.5 mm² twisted pair
|
|
| Zone | ||
|---|---|---|
| Maximum zone capacity |
up to 512
|
|
| Input | ||
|---|---|---|
| Input type and rating |
150 mA (max. Load), Cable type: Recommended 2 core 1.5 mm² twisted pair
|
|
| Programmable |
2
|
|
| Termination |
15 kohm
|
|
| Output | ||
|---|---|---|
| Output type and rating |
Cable type: Recommended 2 core 1.5 mm² twisted pair
|
|
| Termination |
15 kohm
|
|
| Standby battery | ||
|---|---|---|
| Capacity |
Max. 2 x 12 V, 18 Ah (use supplied cables)
|
|
| Physical | ||
|---|---|---|
| Form factor |
Large
|
|
| Physical dimensions |
450 x 581 x 169 mm (W x H x D)
|
|
| Net weight |
7.4 kg (without battery)
|
|
| Shipping weight |
10.1 kg
|
|
| Colour |
Pure white (RAL 9010)
|
|
| Mounting type |
Surface mount
|
|
| Cable entries |
18 (20 mm) / 2 (20 mm) / 2 removable plates (Top /Bottom/Back)
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-8 to +42°C
|
|
| Storage temperature |
-10 to +50°C
|
|
| Relative humidity |
95% max. noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP30: for indoor use only
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
BS5839-1
CPD
LPCB
NBNS21-100
NEN2535
RoHS
WEEE
|
|
| Certification |
EN54-13
EN54-2
EN54-21
EN54-4
VdS
|
|
| Outputs | ||
|---|---|---|
| Programmable supervised | 2, 750mA / 19.5-28VDC (24VDC nominal) | |
| General Fire + Fault supervised | 2, 350mA / 19.5-28VDC (24 VDC nominal) | |
| General Fire + Fault relay | 2 | |
| Aux | 1 resetable, 500mA / 19.5-28VDC (24VDC nominal) | |
| Cable type | Recommended 2 core 1.5 mm² twisted pair | |
| End of Line resistor | 15kohm | |
| Loops | ||
|---|---|---|
| Outputs | 1, 250 mA / 29VDC (29VDC to 36VDC ) | |
| Cable length | 56ohm / 1µF max. 4 km | |
| Cable type | Recommended 2 core 1.5 mm² twisted pair | |
Downloads
All downloadsDatasheet
Certificates
Technical documentation
User documentation
Quick operation guide
Compatibility list
CPD / CPR
Other EU certificate
Other EU certificate
VMC_B-9212-FD-K872-d_KFP-AF1 series
Other EU certificate
VMC_C1199a-(cl-1)_2X, KFP, ZP2 series
Other EU certificate
VMC_PR-1723/064_KFP-A
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.