KAL760
Kilsen Addressable Input Module - 1 Input
- EN54:18 and CPD certified
- Surface mount
- Easy addressing
- External or loop powered
- Local alarm and communications indication
At a glance
General
The KAL700 series modules consists of a complete range of interfaces developed for I/O control on Kisen addressable fire systems, housed in easy to install, IP55 housings. These modules allow the fire system to perform additional building management functions during fire situations. 125 I/O addresses are available on every fire panel loop in addition to 125 fire detector addresses.
Input Module
The KAL760 is an addressable, single input unit for Kisen addressable fire systems. It provides a remote input to the fire system loop that is constantly monitored for open and short circuit conditions. The input may be activated by closing a potential free contact.
Installation
The KAL700 Series is designed for surface mount installation. Addressing on the modules is done via easy to use DIP switches.
Applications
The KAL760 may be used to monitor both pre-alarm and alarm states of any potential free contact and report this status to the fire control panel e.g. the monitoring of pressure equipment, aspiration systems, flow switches, doors, etc.
Details
- EN54:18 and CPD certified
- Surface mount
- Easy addressing
- External or loop powered
- Local alarm and communications indication
- Normally open switch supervision
- Part of a family of I/O modules consisting of: -Conventional zone monitors -Digital input modules -Extinguishing control modules -Loop Isolators -Manual call points -Relay and supervised output units -Fire door controllers
Technical specifications
| General | ||
|---|---|---|
| Status indication |
LED
|
|
| Compatibility |
Kilsen KL7A systems
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
24 VDC
|
|
| Operating voltage |
22 to 38 VDC
|
|
| Current consumption |
Loop power:
750 µA (Quiescent)
<3.6 mA (Active)
External power:
110 µA @ 24 VDC from the loop (Quiescent)
135 µA @ 35 VDC from the loop (Quiescent)
200 µA (Quiescent)
<10 mA (Active)
|
|
| Input | ||
|---|---|---|
| Input quantity |
1
|
|
| Input type and rating |
Supervised
|
|
| Input states |
Active
Normal
Open
Short
|
|
| Pre-alarm resistor |
100 kΩ
|
|
| Alarm resistor |
39 kΩ
|
|
| Termination resistor |
270 kΩ
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
150 x 110 x 70 mm
|
|
| Net weight |
370 g
|
|
| Colour |
Grey
|
|
| Mounting type |
19" rack
Surface mount
|
|
| Cable entries |
10
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +50°C
|
|
| Storage temperature |
-10 to +70°C
|
|
| Relative humidity |
10 to 95% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP55
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 2
WEEE
|
|
| Certification |
CPR
|
|
| Standards |
EN54-18
|
|
Downloads
All downloadsDatasheet
Installation sheet
Certificates
CPD / CPR
Other EU certificate
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.