DCD-1E-IS(WHT)
Conventional Intrinsically Safe Heat Detector, Grade A1R
- Twin fire LEDs allow 360° viewing
- Remote indicator output
- ATEX classification to II 1G EEx ia IIC T5 Tamb=55°C
- Suitable for installation in areas at Category 1 (including all lower categories)
- Approved by LPCB and GL
Related products
At a glance
General
The DCD-1E-IS(WHT) is a WHITE intrinsically safe conventional rate of rise heat detector with a 60°C fixed temperature element designed for use in hazardous areas. The unit also features a remote indicator output.
Heat detectors are normally used in applications where smoke detectors are unsuitable or if there is a danger of nuisance alarms from smoke detectors.
Heat detectors are normally used in applications where smoke detectors are unsuitable or if there is a danger of nuisance alarms from smoke detectors.
Heat Detector Classification
Heat detectors are classified according to the highest ambient temperature in which they can safely be used without risk of false alarm. The classes are identified by the letters A to G. In addition to the basic classification, detectors may be identified by a suffix to show that they are rate-of-rise (suffix R) or fixed temperature (suffix S) types.
A1R
A1 - Detector Class (Max. Application Temperature = 50°C, Static Response Temperature 54-65°C)
R - Temperature Response (with Rate of Rise)
A1R
A1 - Detector Class (Max. Application Temperature = 50°C, Static Response Temperature 54-65°C)
R - Temperature Response (with Rate of Rise)
Hazardous Area Classification
ATEX II 1G
II - Equipment group (Non-Mining)
1 - Equipment category (for Zone 0 or 20)
G - Type of explosive atmosphere (Gas, Vapours and Mist)
Cenelec EEx ia IIC T5 Tamb = 55°C
E - Conformity with European standard
Ex - Explosion protection symbol
ia - Protection concept (Intrinsically Safe)
IIC - Apparatus Group (Gas)
T5 - Temperature classification (100°C)
Tamb - Maximum ambient temperature (55°C)
II - Equipment group (Non-Mining)
1 - Equipment category (for Zone 0 or 20)
G - Type of explosive atmosphere (Gas, Vapours and Mist)
Cenelec EEx ia IIC T5 Tamb = 55°C
E - Conformity with European standard
Ex - Explosion protection symbol
ia - Protection concept (Intrinsically Safe)
IIC - Apparatus Group (Gas)
T5 - Temperature classification (100°C)
Tamb - Maximum ambient temperature (55°C)
BASEEFA Certificate number
ATEX - BAS01ATEX1021
Details
- Twin fire LEDs allow 360° viewing
- Remote indicator output
- ATEX classification to II 1G EEx ia IIC T5 Tamb=55°C
- Suitable for installation in areas at Category 1 (including all lower categories)
- Approved by LPCB and GL
Technical specifications
| General | ||
|---|---|---|
| Status indication |
LED
|
|
| User interface |
LED
|
|
| Compatibility |
Aritech, Kilsen & Ziton conventional zone interfaces
|
|
| Connectivity |
2-wire zone
|
|
| Electrical | ||
|---|---|---|
| Power supply type |
Zone powered
|
|
| Operating voltage |
15 to 30 VDC
|
|
| Current consumption |
50 µA (quiescent)
<50 mA (alarm)
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Termistor
|
|
| Monitoring |
Open circuit
Short circuit
|
|
| Zone length |
Zone configuration dependent
|
|
| Rate-of-rise |
Yes
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
100 x 40 mm (Ø x H)
|
|
| Net weight |
97 g
|
|
| Colour |
White
|
|
| Mounting type |
Base mount
Ceiling mount
|
|
| Material (body) |
ABS
|
|
| Functional marking |
BASEEFA Rating
|
|
| Environmental | ||
|---|---|---|
| Vandal proof |
No
|
|
| Operating temperature |
-10 to +55°C
|
|
| Storage temperature |
-30 to +70°C
|
|
| Relative humidity |
<95% noncondensing @ 40°C
|
|
| Environment |
Indoor
IS
|
|
| Hazardous environment rating |
II 1G EEx ia IIC T5 Tamb=55°C
|
|
| IP rating |
IP63
|
|
| Regulatory | ||
|---|---|---|
| Compliancy |
CE
REACH
RoHS 2
|
|
| Certification |
CENELEC/ATEX
EN54-5
|
|
Downloads
All downloadsDatasheet
Other EU certificate
Other EU certificate
IECex Certificate of Conformity
Other EU certificate
Other EU certificate
Other EU certificate
Schedule to ATEX Quality Assurance Notification / IECEx Quality Assessment Report
Certificates
Installation sheet
CPD / CPR
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.