Skip to main content

DT713-7

ARITECH Dx700 Series conventional high temperature heat detector
  • Automatic self diagnostics: Dynamic full detector and sensitivity test
  • High false alarm immunity
  • 12 to 24 VDC operation
  • Polarity insensitive
  • Part of a full range: Optical, heat and optical/heat multi criteria detectors
View all

At a glance

General

The 700 series conventional detector line includes a range of temperature detectors:
• The DT713-5 is a class A2 temperature detector with a fixed temperature threshold of 57°C and built in rate-or-rise functionality.
• The DT713-5R has the same specifications as the DT713-5, but in addition includes a built in potential free changeover relay
• The DT713-7 is a class B temperature detector with a fix temperature threshold of 70°C and built in rate-or-rise functionality.

Preventing false alarms with self diagnostics

700 Series detectors continually monitor their own sensitivity and operational status. Once a day they perform a full diagnostic test that includes dynamically testing the sensing chamber and internal electronics. Any abnormal statuses are reported locally on a fault LED on the detector, and signalled back to a compatible CIE.

The detector base

Every 700 series base features a continuity link between LINE IN (1) and LINE OUT (2) terminals of the conventional detector circuit. The base is supplied with the link in closed position. The link is enabled by default allowing you to check the zone wiring using only the bases. The link will automatically disconnect when a detector is inserted, allowing the panel to generate a fault message when the detector is removed.

Details

  • Automatic self diagnostics: Dynamic full detector and sensitivity test
  • High false alarm immunity
  • 12 to 24 VDC operation
  • Polarity insensitive
  • Part of a full range: Optical, heat and optical/heat multi criteria detectors
  • EN54 approved and CPR certified

Technical specifications

General
Status indication
Red LED (alarm)
User interface
LED
Compatibility
Aritech conventional systems & Aritech and Excellence conventional ZMUs
Reset voltage
<2.5 V
Reset time
1 s
Alarm levels
1
Connectivity
2-wire zone & remote indicator
Electrical
Power supply type
Zone powered
Operating voltage
8.5 to 33 VDC
Current consumption
100 µA (quiescent at 24 VDC)
<60 mA (in alarm at 24 VDC)
Detection
Detection principle
Heat
Sensitivity
Category B
Zone length
Cable dependent
Alarm temperature (typical)
+70°C ± 1.5°C
Rate-of-rise
8°C/min above 40°C
Output
Output quantity
1
Remote alarm output
Indicator
Physical
Physical dimensions
100 x 50 mm (Ø x H)
Net weight
85 g
Colour
Cloud white (RAL 9001)
Mounting type
Ceiling mount
Material (body)
Plastic
Environmental
Vandal proof
No
Operating temperature
-10 to 65°C
Storage temperature
-10 to +70°C
Application temperature (maximum)
+65°C
Application temperature (typical)
+40°C
Relative humidity
0 to 95% noncondensing
Environment
Indoor
IP rating
IP43
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-5