Skip to main content

DP2061T

ARITECH 2000 Series addressable multisensor fire detector
  • Optical enhanced by heat, smoke detector
  • Full diagnostic self testing
  • Five independently controlled modes of operation:
    • Multisensor with 2 selectable smoke sensitivities
    • Dual sensor (independent optical and A2R heat)
    • Optical sensor only (EN54-7 approved)
    • Heat sensor only (A2R - 60°C with rate-of-rise)
  • Enhanced digital communication protocol
  • Remote signaling capabilities
View all

At a glance

General

The DP2061T multi-sensor combines the smoke sensitivity of an optical smoke detector with the enhancement of heat sensing. Being able to operate in 5 dynamically changeable modes that are fully controlled and programmable from the fire alarm panel, the DP2061T can operate as an optical smoke detector enhanced by heat detection (with two different smoke sensitivities), as a dual smoke and A2R heat detector – each sensor operating independently, as an optical detector only (EN54-7 certified), or as a A2R heat detector only.

Multimode operation

The five modes may be controlled by day/night mode operation for each sensor. The detector may, for example, operate as a heat detector during the day in an occupied building, and at high sensitivity of smoke with heat at night when the building is not occupied. Each sensor may be controlled independently.

A full range

The DP2061T multi-sensor is part of the 2000 series family. This series includes optical smoke and heat detectors, IO units, a full line of manual call points, standard and isolator bases.

Maintenance friendly

The DP2061T multi-sensor has all the maintenance features of the 2000 series detectors. It features the field replaceable optical block, allowing the cleaning of the optical chamber on site without the need for recalibration. A self-test feature as well as drift compensation and contamination warning is provided when used with compatible Aritech fire panels.

State of the art communication

An enhanced protocol ensures the overall integrity and error-free operation of the system, without compromising speed. The 2000 series protocol provides features such as CRC error checking and multiple bus cycle codes to enable advanced features of the panel to detector communication.

Details

  • Optical enhanced by heat, smoke detector
  • Full diagnostic self testing
  • Five independently controlled modes of operation: • Multisensor with 2 selectable smoke sensitivities • Dual sensor (independent optical and A2R heat) • Optical sensor only (EN54-7 approved) • Heat sensor only (A2R - 60°C with rate-of-rise)
  • Enhanced digital communication protocol
  • Remote signaling capabilities
  • Easy numeric addressing (1-128) for fast and fault free installation
  • Field exchangeable optical chamber for easy on-site maintenance

Technical specifications

General
Status indication
Dual red alarm LED
Compatibility
Aritech 2000 series systems
Alarm levels
5
Connectivity
2000 Series detector bases
Addressing method
Rotary switch
Electrical
Power supply type
Loop powered
Operating voltage
17 to 28 VDC
Current consumption
350 µA (quiescent at 24 VDC)
4 mA (alarm at 24 VDC)
Detection
Detection principle
Optical light scatter and/or heat
Monitoring
Alarm threshold
Contamination level
Sensitivity
Configurable
Coverage area
<80 m²
Rate-of-rise
Class A2 compliant
Output
Output quantity
1
Output type and rating
Remote indicator
Programmable
No
Remote alarm output
4 mA
Physical
Physical dimensions
100 x 50 mm (Ø x H)
Net weight
115 g
Colour
Cloud white (RAL 9001)
Mounting type
Base mount
Material (body)
Plastic
Environmental
Vandal proof
No
Operating temperature
-10 to +60°C
Storage temperature
-10 to +70°C
Application temperature (typical)
+25°C
Relative humidity
10 to 95% noncondensing
Environment
Indoor
IP rating
IP23
Regulatory
Compliancy
CE
REACH
RoHS 2
WEEE
Certification
CPR
Standards
EN54-7